ZW32-12 outdoor on-column vacuum circuit breaker

Product Details
Product overview
ZW32 type outdoor column vacuum circuit breaker (below) for rated voltage 12KV, three-phase AC 50Hz outdoor high-voltage power distribution equipment.
It is mainly used for the load current, overload current and short-circuit current in the power system. It is suitable for protection and control in substations and distribution systems of industrial and mining enterprises, and is more suitable for urban and rural power grid construction and transformation and frequent operation places.
Model meaning
ZW |
32 |
12 |
T |
630 |
25 |
Outdoor on-column vacuum circuit breaker |
Design serial number: 32 (pole type) |
Rated voltage: 12kV |
spring operating mechanism |
Rated current: 630A |
Short-time withstand current: 25kA |
Working conditions
Altitude: ≤ 2000m and below;
Ambient air temperature: upper limit 30°C, lower limit -40°C;
The wind pressure does not exceed 700Pa (equivalent to 34 m/s);
Amplitude: inconstant violent vibration;
Anti-pollution level III.
Technical parameters
Project |
Unit |
Parameter Value |
Rated voltage |
kV |
12 |
Rated frequency |
Hz |
50 |
Rated current |
A |
630 |
Temperature rise test current |
1.1lr |
|
Rated power frequency Imin withstand voltage (relative to ground) |
kV |
42 |
Rated power frequency Imin withstand voltage (fracture) |
kV |
48 |
Peak rated lightning impulse withstand voltage (relative to ground) |
kV |
75 |
Peak rated lightning impulse withstand voltage (port) |
kV |
85 |
Rated short-time withstand current |
kA |
25 |
Rated short-time withstand current duration |
s |
4 |
Rated peak withstand current |
kA |
63 |
Loop resistance |
Ц Ω |
≤200 |
Mechanical life |
10000 |
|
Partial discharge (1.1Ur) |
≤ 10pC |
|
Protection level |
IP65 |
Key words:
ZW32-12 outdoor on-column vacuum circuit breaker
Related Products