

ZGS11-12 combined transformer station (US transformer)

Product Details
Product overview
ZGS11 series combined transformer is a domestic and American box transformer launched by our company. Since the successful research and development, the company has been carefully built for many years. As an important power supply unit in urban and rural power distribution networks, this product is a power distribution product integrating high-voltage control substation and power distribution equipment, and is widely used in urban and rural power distribution networks.
The product will be high-voltage load switch, high-voltage fuse placed in the transformer oil, with the transformer body co-box or sub-box two structural forms. The oil tank adopts a fully sealed structure and is equipped with oil temperature gauge, oil level gauge, pressure gauge, pressure relief valve, oil drain valve and other components to monitor the operation status of the transformer. The product is divided into ring network type, terminal type and dual power supply mode.
Model meaning
ZG |
S |
11 |
With (H) |
Mouth |
10 |
"Group" and "common" box-type transformers |
three-phase |
Performance Level Code |
High voltage wiring scheme; Z is terminal and H is ring network. |
Capacity (KVA) |
High voltage level (KV) |
Working conditions
Ambient temperature: maximum temperature 40°C, minimum temperature -30°C;
Altitude: ≤ 1000m;
Wind speed: equivalent to 34 m/s (not more than 700Pa);
Humidity: average daily relative humidity <95%; Average monthly relative humidity <95%;
Anti-vibration: horizontal acceleration is not more than 0.4 m/s.2, the vertical acceleration is not more than 0.15 m/s2;
Installation site inclination: not more than 3 °;
Installation environment: the surrounding air is not obviously polluted by corrosive and flammable gases, and there is no violent vibration at the installation site.
Technical parameters
Project |
Unit |
Parameters |
|
Rated voltage |
kV |
10/0.4 (high pressure/low pressure) |
|
Maximum operating voltage |
kV |
12 (high pressure side) |
|
Rated frequency |
Hz |
50 |
|
Rated capacity |
kVA |
50-1600 |
|
1 minute power frequency withstand voltage |
kV |
35 |
|
lightning impulse voltage |
kV |
75 |
|
Cooling mode |
oil-immersed self-cooling |
||
Breaking current of HV backup fuse |
kA |
50 |
|
Breaking current of plug-in fuse |
kA |
2.5 |
|
Ambient temperature |
°C |
-35 to 40 |
|
Allowable temperature rise of coil |
°C |
65 |
|
No-load voltage regulation |
± 5% or ± 2X2.5% |
||
Noise level |
db |
50 |
|
Protection level |
IP43 |
Key words:
ZGS11-12 combined transformer station (US transformer)
Related Products