ZW20-12 outdoor on-column vacuum circuit breaker
ZW20-12 outdoor on-column vacuum circuit breaker
+
  • ZW20-12 outdoor on-column vacuum circuit breaker
  • ZW20-12 outdoor on-column vacuum circuit breaker

ZW20-12 outdoor on-column vacuum circuit breaker

ZW20-12 type outdoor high voltage vacuum circuit breaker (hereinafter referred to as "circuit breaker") is rated voltage 12kV, three-phase AC 50Hz outdoor power distribution equipment. Vacuum arc extinguishing and SF & gas are used as the insulation medium. It is mainly used to open and close the load current, overload current and short-circuit current of agricultural network, urban network and small power system. The overall structure of the product is three-phase common box, three-phase vacuum interrupter is placed in the metal box, variable pressure performance is reliable, high insulation strength.
Certification

Category:

Telephone:

Product Details


Product Summary

ZW20-12 type outdoor high voltage vacuum circuit breaker (hereinafter referred to as "circuit breaker"Rated voltage 12kV, three-phase AC 50Hz outdoor distribution equipment. Vacuum arc extinguishing and SF & gas are used as the insulation medium. It is mainly used to open and close the load current, overload current and short-circuit current of agricultural network, urban network and small power system. The overall structure of the product is three-phase common box, three-phase vacuum interrupter is placed in the metal box, variable pressure performance is reliable, high insulation strength.

 

Model meaning

ZW

20

12

T

630

25

Outdoor on-column vacuum circuit breaker

Design serial number: 20 (box type)

Rated voltage: 12kV

spring operating mechanism

Rated current:

630A

Short-time withstand current:

25kA

 

Working conditions

Altitude: not more than 2000m;

Surrounding air temperature:-40°C ~ 40°C, daily temperature difference: daily temperature change is not more than 25°C;

Wind speed: not more than 35 m/s;

No flammable, explosion hazard, strong chemical corrosion (such as various acids, alkalis or smoke, etc.) and violent vibration of the place.

 

Technical parameters

Project

Unit

Parameter Value

Rated voltage

kV

12

Rated frequency

Hz

50

Rated current

A

630

Temperature rise test current

 

1.1lr

Rated power frequency Imin withstand voltage (relative to ground)

kV

42

Rated power frequency Imin withstand voltage (fracture)

kV

48

Peak rated lightning impulse withstand voltage (relative to ground)

kV

75

Peak rated lightning impulse withstand voltage (port)

kV

85

Rated short-time withstand current

kA

25

Rated short-time withstand current duration

s

4

Rated peak withstand current

kA

63

Loop resistance

μΩ

≤120

Mechanical life

 

10000

Partial discharge (1.1Ur)

 

≤ 10pC

Protection level

 

IP67

Rated pressure of SF6 gas (20°C gauge pressure)

MPa

0

Annual leakage rate of SF6 gas

 

<0.1%

 

Key words:

ZW20-12 outdoor on-column vacuum circuit breaker

Get Quote

Note: Please leave your contact information and our professionals will contact you as soon as possible!

Submit immediately