HY5WS-17/50 Lightning Arrester Series

Product Details
Product overview
Composite jacket metal oxide arrester is a kind of advanced protection device to limit overvoltage. It is widely used in power generation, transmission, substation and distribution system to protect the insulation of electrical equipment from overvoltage damage.
Composite coat metal oxide arrester it not only has the advantages of porcelain metal oxide arrester, but also has good electrical insulation performance, high dielectric strength, anti-leakage, anti-corrosion, heat resistance, cold resistance, aging resistance; explosion-proof, hydrophobic, sealing and other advantages.
The drop type (drop type, removable type) lightning arrester is cleverly installed on the drop type mechanism of the drop type fuse after modification of the distribution type zinc oxide lightning arrester, so that under the condition of continuous power supply, the lightning arrester can be easily detected, repaired and replaced with the help of the insulating switch lever, which not only ensures the smooth flow of the line, but also greatly reduces the working intensity and time of the power maintenance personnel, it is especially suitable for places that are not suitable for power outages, such as communications, airports, stations, hospitals, and prosperous commercial areas. Other performance of the product is the same as that of the distribution type arrester.
Model meaning
H |
Y |
5 |
W |
S |
17 |
15 |
composite material (Jacket silicone rubber) |
Jin Zeng |
Nominal discharge current |
No gap |
Distribution type surge arrester |
Surge arrester rated voltage 17kV |
Residual arrester voltage 50kV |
Working conditions
Ambient temperature: not less than 40°C, not more than 60°Co
The altitude is not more than 3000m, beyond 3000m can be specially made according to the actual situation.
Power frequency: 48Hz ~ 62Hz
Maximum wind speed: no more than 35 m/s
Earthquake intensity: 7 degrees and below
The voltage applied to the arrester for a long time cannot exceed its rated voltage.
The air at the installation site should not contain chemically corrosive gases, vapors, or explosive dust, if any, and should be noted when ordering.
Working conditions
Project |
Unit |
Parameters |
|
System rated voltage |
kV |
10 |
|
Rated voltage of lightning arrester |
kV |
17 |
|
Rated controller car |
Hz |
50 |
|
Continuous operating voltage |
kV |
13.6 |
|
Current 1mA Reference Voltage |
kV |
E25 |
|
Leakage current at 0.75 DC reference voltage |
uA |
Lan 50 |
|
8/20us lightning impulse current residual voltage |
kV |
GO |
|
30/80US operation impulse current residual voltage |
kV |
< 42.5 |
|
1/lOus steep impulse current residual voltage |
kV |
W57.5 |
|
Rated short-time power frequency withstand voltage |
Dry state |
kV |
42 |
Wet state |
30 |
||
Rated lightning impulse withstand voltage (peak) |
kV |
75 |
|
Nominal discharge current |
kA |
5 |
Key words:
HY5WS-17/50 Lightning Arrester Series